Short answer: both an HRV (heat recovery ventilator) and an ERV (energy recovery ventilator) bring in fresh outdoor air, exhaust the same amount of stale air, and recover heat between the two streams. An ERV also moves some moisture. In a tight Western New York house with central air, an ERV is usually the better match, because winters are very dry and summers are humid. An HRV still fits a house that runs humid in winter. Either one only helps if it is sized, ducted and balanced properly.

What each one does

DOE’s Building Science Education program describes both as balanced ventilation with a heat exchanger, fans and controls. The difference is moisture:

HRV ERV
Recovers heat between airstreams Yes Yes
Moves water vapor between airstreams No Some
Winter effect on indoor humidity Exhaust takes indoor moisture out; dry outdoor air comes in, so the house trends drier Returns part of the indoor moisture to the incoming air, so the house stays less dry
Summer effect Humid outdoor air comes in with its moisture Part of the outdoor moisture is kept out of the incoming air
Does it dehumidify the house? No No. It limits moisture coming in; it does not remove moisture already inside

Choosing for a Buffalo-type climate

Erie County is in Climate Zone 5: long heating seasons, but humid summers. That is exactly where the HRV-vs-ERV debate lives.

A useful framework comes from Patrick Huelman’s 2019 cold-climate ventilation presentation (an expert view, not a regulation):

  • Energy only: HRVs for heating-only climates, ERVs for cooling or mixed climates.
  • Indoor humidity: an HRV can over-dry a leaky or low-moisture house. An ERV may not dry down a tight house with a lot of indoor moisture.
  • High-performance new homes with AC: go with an ERV, because summer moisture is the harder problem.

The old worry about ERVs in cold climates was frost. The Cold Climate Housing Research Center monitored eight ERVs through a Fairbanks, Alaska winter and found none failed from frost. That does not mean any ERV works anywhere. It means a unit with a proper defrost strategy can.

Put together, a practical way to decide:

Your house in winter (with a hygrometer) Leans toward
Dry: RH in the low 20s or below, people complaining of dry air ERV
Comfortable: 30s on cold days, no window condensation Either; ERV if you have central AC and humid summers
Humid: windows fog or frost, musty smell, lots of occupants or cooking HRV, or an ERV plus better spot exhaust. Find the moisture source either way

Read our winter dryness guide for how to measure and what normal looks like.

Do you need one at all?

Many older Buffalo houses are leaky enough that outdoor air gets in on its own, in an uncontrolled way. DOE’s consumer guide describes three options: natural ventilation (leaks and windows), spot ventilation (bath and kitchen fans), and whole-house systems. Whole-house systems come in three kinds: exhaust-only, supply-only or balanced. HRVs and ERVs are balanced.

  • Leaky house, no plans to tighten it: good, quiet bath and kitchen fans ducted outdoors may be all you need.
  • House being air-sealed, re-insulated or getting new windows: DOE recommends considering controlled ventilation after you air seal. This is where an HRV or ERV is worth pricing.
  • New construction or a gut renovation in New York: the 2025 Residential Code of New York State took effect December 31, 2025. Its Section R325.3 requires mechanical ventilation for dwelling units that comply with the energy code’s air-leakage section. Your builder, designer or local code official decides what applies to your permit. We are describing the code, not interpreting your project.

The Home Ventilating Institute notes that exhaust-only systems are appropriate in temperate to cold climates. A continuous, quiet bath fan is a legitimate, cheaper whole-house strategy in some houses. The trade-off is that its replacement air comes in through leaks, not through a filter or heat exchanger.

What a good installation includes

DOE’s Building America checklist for balanced HRV/ERV installations is the best public spec we found. Highlights:

  • Airflow target for continuous operation: 50 cfm up to 1,500 sq ft, 70 cfm for 1,501–2,500 sq ft, 100 cfm above 2,500 sq ft.
  • Filtration: outdoor air filtered at MERV 11 or higher, with the filter easy for you to reach.
  • Separation: the exhaust outlet at least 10 feet from any air inlet, and not blowing onto a walkway.
  • Ducts: sealed with mastic or UL 181 tape; ducts outside the insulated envelope insulated to at least R-8.
  • If it ties into the furnace ducts: a damper to stop air flowing backward through the ventilator when it is off.
  • Room coverage: each occupied room with a door should have a ducted supply, a ducted return, or both.
  • Commissioning: the installer measures the delivered airflow with a flow hood, flow grid or anemometer, and walks you through filter and intake-screen maintenance.

The Home Ventilating Institute adds the cold-climate item: frost protection good enough to keep the unit ventilating all winter. Ask which defrost method the unit uses, and where the condensate goes if the unit has a drain.

Questions to put to an installer:

  1. What airflow is this sized for, and how will you measure it after installation?
  2. Is it a dedicated duct system, or does it use the furnace ducts? If it uses the furnace ducts, does the furnace blower have to run for the ERV to deliver air?
  3. How is it balanced, so supply and exhaust match?
  4. What is the defrost strategy, and is there a condensate drain?
  5. What filters does it take, and how often do they need changing?

What it will and will not fix

  • Will: steady, controlled fresh air; lower stale-air and odor buildup; less winter drying than an HRV (ERV); less summer moisture entry than an HRV (ERV).
  • Will not: dehumidify a damp basement. See whole-house vs. portable dehumidifiers.
  • Will not: replace kitchen and bath exhaust at the source.
  • Will not: work well if it is installed without balancing or with filters that are never changed.

What we are not claiming

  • We do not publish installed prices. Cost depends on whether the ventilator gets its own ducts.
  • We do not name a “best” brand. Look for HVI-certified ratings and a cold-climate defrost strategy.
  • Code requirements here are summarized from the 2025 Residential Code of New York State as published. Your local building department is the authority for your permit.

In Western New York? If you are tightening up a house or adding a ventilator, you can ask Radiant Mechanical for an estimate. David Stoehr, who reviews this site, owns Radiant Mechanical.