Short answer: SEER2 and HSPF2 are useful for comparing like with like, and they are what rebates and certification programs reference. But each is a single seasonal average built on a standard test and a standard reference climate. For a Western New York winter, the numbers to add are the rated heating capacity and COP at 5°F for the exact indoor and outdoor pair, plus a load calculation for your house.
What the two numbers are
Both appear in the ENERGY STAR heat pump criteria and in the federal test procedure.
- SEER2 is the total heat removed from the conditioned space during the annual cooling season, in Btu, divided by the total electrical energy consumed, in watt-hours. It is a cooling number.
- HSPF2 is the total space heating required in Region IV during the heating season, in Btu, divided by the total electrical energy consumed by the heat pump system during the same season, in watt-hours. It is a heating number.
The “2” means they were measured under the current federal test procedure, Appendix M1 (based on AHRI 210/240-2024), rather than the older procedure that produced SEER and HSPF. Older and newer values are not interchangeable. The U.S. Department of Energy has also adopted newer metrics, SCORE and SHORE, but testing to them is not required until compliance is required with amended standards based on them. Until then, SEER2 and HSPF2 are what you will see on quotes.
What HSPF2 is not
HSPF2 for federal compliance is calculated with the fractional heating bin hours for Region IV. In AHRI’s words, HSPF2 varies depending on the region, and the one used to evaluate compliance is based on Region IV. Other regions are optional representations in the federal rule. If a quote does not say which region an HSPF2 uses, assume it is the standard compliance value.
So an HSPF2 on a quote is a seasonal efficiency figure from a standard reference climate. We have not tried to translate it into Buffalo operating cost, because the arithmetic depends on your house and rates. For an illustration of a real cost comparison, see the dual-fuel balance-point guide. A separate, official climate figure for sizing — not for computing HSPF2 — is NOAA’s Engineering Weather Data for Buffalo Niagara International Airport, which lists a 99.0% heating dry-bulb of 7°F and a 99.6% value of 3°F (period of record 1988–2017, checked November 27, 2026). Manual J and ASHRAE Handbook tables used in a given load calculation may differ.
What ENERGY STAR requires
ENERGY STAR’s criteria currently list:
| Category | Minimums |
|---|---|
| Standard certified split systems | ≥ 7.8 HSPF2, ≥ 15.2 SEER2, ≥ 11.0 EER2 |
| Standard certified single-package | ≥ 7.2 HSPF2, ≥ 15.2 SEER2, ≥ 10.0 EER2 |
| Cold Climate, split, non-ducted | ≥ 8.5 HSPF2, ≥ 15.2 SEER2 |
| Cold Climate, split, ducted | ≥ 8.1 HSPF2, ≥ 15.2 SEER2 |
| Cold Climate, single package | ≥ 8.1 HSPF2, ≥ 15.2 SEER2 |
To earn the Cold Climate designation, a unit must also show:
- COP at 5°F of at least 1.75, measured with the Appendix M1 H4₂ test.
- Heating capacity at 5°F of at least 70% of its capacity at 47°F.
- A controls verification procedure confirming the 5°F results are achieved by the native controls as they would operate in a customer’s home.
Those last items are about cold weather, and the seasonal HSPF2 does not show them. Two heat pumps with similar HSPF2 can have different capacity retention at 5°F. For Western New York, a unit that meets ENERGY STAR Cold Climate is a reasonable starting screen, and the actual rated 5°F values for your pair are the next step. Our cornerstone guide explains why 1.75 is a floor and not a target.
What neither number tells you
- Capacity at your design temperature. Neither value says whether the unit can carry your house’s heating load on a very cold night. That takes a Manual J-style load calculation and the manufacturer’s capacity data for the matched pair. See how to read an HVAC quote.
- The match. Ratings apply to a specific outdoor and indoor combination. A quote that lists only the outdoor model cannot be checked.
- Installation quality. Duct leakage, airflow, charge, and controls setup are outside the rating.
- Your bill. Utility rates, thermostat habits, and house leakage determine it.
- Backup heat use. Neither rating says how often the system will lean on auxiliary heat. See why “Emergency Heat” is not a daily setting.
How to use the numbers
- Treat HSPF2 and SEER2 as screening numbers to compare comparable systems and to check that rebate eligibility is plausible. Check the exact incentive terms in the New York incentives guide.
- Ask for capacity and COP at 47°F, 17°F, and 5°F for the exact pair, and confirm the source is a manufacturer or certification listing.
- Ask what outdoor temperature the heat pump alone is sized to carry, and what covers the rest.
What we are not claiming
We have not published ratings for named models, or a conversion from HSPF2 to a dollar figure. Those need a specific model and a dated source, or a load calculation for your home. The NOAA 7°F / 3°F heating design values above are a published station reference, not a substitute for the design temperature on a particular quote.